Example to calculate short circuit current for circuit breaker
The purpose of this write-up is to help the reader estimate the example before you hire the PE to do the official calculation.
All electrical systems are susceptible to short circuits. The short circuit currents can produce considerable thermal and mechanical stresses in electrical distribution equipment. Therefore, it’s important to protect personnel and equipment by calculating short-circuit currents during system upgrade and design. Since these calculations are life-safety related, they’re mandated by 110.9 of the NEC.
In the example shown in Fig. 1, our goal is to find the irrupt rating for the two breakers (1600A and 250A), and also find the withstand rating of the two panels (main and sub-panel).
Table (1): These values are equal to one over the impedance per foot, based upon resistance and reactance, found in IEEE std. 241 |
F = (1.73 *50 *24,506) / (28,303*5*480) = 0.031206
M = 1/(1+F) = 0.969738; where M is the multiplier
I S.C. 3 ph for point 2 = 24506* M = 24506*0.969738 = 23,764 A or 23.7 KA (this is the available short circuit current at point 2)
It’s worth mentioning that the further the main panel is from the transformer, the lower the short circuit current, but you will have a bigger voltage drop, due to the larger line impedance.
The calculation below will show the short circuit current at point 3 (this is similar to the point 2 calculation):
F = (1.73 * L* I S.C. 3 ph at point 2 ) / (C *n*V L-L)
F = (1.73 *100*23,764) / (16673*1*480) = 0.51370
M = 1/(1+F) = 1/1.51370 = 0.6606
I S.C 3 ph for point 3 = 23,764 *0.6606 = 15,699 A or 15.7 KA
I hope you find this example and the short circuit calculation useful. Please let me know if you have any questions.